Specifications, Input – Rockwell Automation 1762-IF4 MicroLogix Analog Input Module User Manual
Page 20
![background image](/manuals/579810/20/background.png)
20 MicroLogix 1762-IF4 Analog Input Module
Publication 1762-IN012C-EN-P - June 2013
Specifications
Input
Attribute
Value
Number of inputs
4 differential (bipolar)
A/D converter type
Sigma-Delta
Common mode voltage range
(1)
(1)
For proper operation, both the plus and minus input terminals must be within ±27V of analog common.
±27V
Common mode rejection
(2)
(2)
V
cm
= 1 V
pk-pk
AC
> 55 dB @ 50 and 60 Hz
Non-linearity (in percent full scale)
±0.12%
Typical overall accuracy
(3)
(3)
V
cm
= 0 (includes offset, gain, non-linearity and repeatability error terms)
±0.32% full scale @ -20…65 °C (-4 °F…149 °F)
±0.24% full scale @ 25 °C (77 °F)
Input impedance
Voltage terminal: 200K
Ω
Current terminal: 275
Ω
Current input protection
±32 mA
Voltage input protection
±30V
Channel diagnostics
Over or under range or open circuit condition by bit reporting for
analog inputs.