Configuration data file – Rockwell Automation 1762-IF4 MicroLogix Analog Input Module User Manual
Page 17

MicroLogix 1762-IF4 Analog Input Module 17
Publication 1762-IN012C-EN-P - June 2013
The bits are defined as follows:
• Sx = General status bits for channels 0…3. This bit is set when an error (over- or
under-range) exists for that channel, or there is a general module hardware error.
• Ox = Over-range flag bits for channels 0…3. These bits are set when the input signal is
above the user-specified range. The module continues to convert data to the maximum
full range value during an over-range condition. The bits reset when the over-range
condition clears.
• Ux = Under-range flag bits for input channels 0…3. These bits are set when the input
signal is below the user-specified range. The module continues to convert data to the
maximum full range value during an under-range condition. The bits reset when the
under-range condition clears.
• SGNx = The sign bit for channels 0…3.
Configuration Data File
The configuration of the format for analog inputs is made at going to run (GTR). Changes made
to the configuration file while in run mode have no effect.
The configuration table is shown below.
Bit 15 and Bits 7
…
4 - Reserved
These bits are reserved and are not checked by the module.
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
reserved
Data Format
Channel 0
Type/Range Select
Channel 0
reserved
Filter Select
Channel 0
1
Data Format
Channel 1
Type/Range Select
Channel 1
reserved
Filter Select
Channel 1
2
Data Format
Channel 2
Type/Range Select
Channel 2
reserved
Filter Select
Channel 2
3
Data Format
Channel 3
Type/Range Select
Channel 3
reserved
Filter Select
Channel 3
4
reserved
5
reserved
6
reserved
7
reserved