Error codes – Rockwell Automation 1762-IF4 MicroLogix Analog Input Module User Manual
Page 19

MicroLogix 1762-IF4 Analog Input Module 19
Publication 1762-IN012C-EN-P - June 2013
Error Codes
The 1762-IF4 module notifies the controller of critical and non-critical errors. The module
condition array word 0 contains the error codes that are generated by the module, as shown
below.
The table below describes the module error codes.
“Don’t Care” Bits
Module Error
Extended Error Information
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Hex Digit 4
Hex Digit 3
Hex Digit 2
Hex Digit 1
Error Type
Hex
Equivalent
(1)
(1)
X represents “Don’t Care”.
Module
Error Code
Extended Error
Information Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no
additional information
X201
001
0 0000 0001
Power-up reset state
Hardware-
Specific Error
X300
001
1 0000 0000
Reserved
Configuration
Error
X400
010
0 0000 0000
General configuration error; no
additional information
X401
010
0 0000 0001
Invalid range select (Channel 0)
X402
010
0 0000 0010
Invalid range select (Channel 1)
X403
010
0 0000 0011
Invalid range select (Channel 2)
X404
010
0 0000 0100
Invalid range select (Channel 3)
X405
010
0 0000 0101
Invalid filter select (Channel 0)
X406
010
0 0000 0110
Invalid filter select (Channel 1)
X407
010
0 0000 0111
Invalid filter select (Channel 2)
X408
010
0 0000 1000
Invalid filter select (Channel 3)
X409
010
0 0000 1001
Invalid format select (Channel 0)
X40A
010
0 0000 1010
Invalid format select (Channel 1)
X40B
010
0 0000 1011
Invalid format select (Channel 2)
X40C
010
0 0000 1100
Invalid format select (Channel 3)