Error codes – Rockwell Automation 1762-IF4 MicroLogix Analog Input Module User Manual

Page 19

Advertising
background image

MicroLogix 1762-IF4 Analog Input Module 19

Publication 1762-IN012C-EN-P - June 2013

Error Codes

The 1762-IF4 module notifies the controller of critical and non-critical errors. The module
condition array word 0 contains the error codes that are generated by the module, as shown
below.

The table below describes the module error codes.

“Don’t Care” Bits

Module Error

Extended Error Information

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Hex Digit 4

Hex Digit 3

Hex Digit 2

Hex Digit 1

Error Type

Hex

Equivalent

(1)

(1)

X represents “Don’t Care”.

Module
Error Code

Extended Error
Information Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no
additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-
Specific Error

X300

001

1 0000 0000

Reserved

Configuration
Error

X400

010

0 0000 0000

General configuration error; no
additional information

X401

010

0 0000 0001

Invalid range select (Channel 0)

X402

010

0 0000 0010

Invalid range select (Channel 1)

X403

010

0 0000 0011

Invalid range select (Channel 2)

X404

010

0 0000 0100

Invalid range select (Channel 3)

X405

010

0 0000 0101

Invalid filter select (Channel 0)

X406

010

0 0000 0110

Invalid filter select (Channel 1)

X407

010

0 0000 0111

Invalid filter select (Channel 2)

X408

010

0 0000 1000

Invalid filter select (Channel 3)

X409

010

0 0000 1001

Invalid format select (Channel 0)

X40A

010

0 0000 1010

Invalid format select (Channel 1)

X40B

010

0 0000 1011

Invalid format select (Channel 2)

X40C

010

0 0000 1100

Invalid format select (Channel 3)

Advertising