Rockwell Automation 1771-IFF/A INSTL.INSTR FAST ANALOG INPUT User Manual

Page 11

Advertising
background image

Publication 1771-IN046B-EN-P - December 2003

Fast Analog Input Module 11

– Jumper all unused channels to module
common to reduce noise.

Channel 1

Channel 2
Channel 3
Channel 4

Channel 5
Channel 6
Channel 7
Channel 8

Channel 9
Channel 10
Channel 1 1

Channel 12

Channel 13
Channel 14

Channel 15
Channel 16

Module Common

Module Common

Module Common

Module Common

Module Common

1771-WG

1
2
3
4
5

6
7

8
9

10

11
12
13

14
15

16

17
18

19
20
21

The 1771-IFF module does not supply loop power for the input
device. The user must supply loop power for loop-powered input devices.

+

The sensor cable must be shielded. The shield must:

extend the length of the cable, but be connected only at the 1771 I/O chassis
extend up to the point of termination

Important:

The shield should extend to the termination point, exposing just enough
cable to adequately terminate the inner conductors. Use heat shrink or
another suitable insulation where the wire exits the cable jacket.

Power
Supply

+

_

– Tie power supply grounds together
to minimize ground loops.

Note: Refer to transmitter manufacturers
specifications for power supply connections.

2-Wire
Transmitter

Power
Supply

Note:

– All module commons are electrically
tied together inside the module.

2-Wire
Transmitter

– Jumper all unused channels to module
common to reduce noise.

Functional Ground

Channel 1

Channel 2
Channel 3
Channel 4

Channel 5
Channel 6
Channel 7
Channel 8

Channel 9
Channel 10
Channel 1 1

Channel 12

Channel 13
Channel 14

Channel 15
Channel 16

Module Common

Module Common

Module Common

Module Common

Module Common

1771-WG

1
2
3
4
5

6
7

8
9

10

11
12
13

14
15

16

17
18

19
20
21

The 1771-IFF module does not supply loop power for the input
device. The user must supply loop power for loop-powered input devices.

+

The sensor cable must be shielded. The shield must:

extend the length of the cable, but be connected only at the 1771 I/O chassis
extend up to the point of termination

Important:

The shield should extend to the termination point, exposing just enough
cable to adequately terminate the inner conductors. Use heat shrink or
another suitable insulation where the wire exits the cable jacket.

+

_

– Tie power supply grounds together
to minimize ground loops.

Note: Refer to transmitter manufacturers
specifications for power supply connections.

Note:

– All module commons are electrically
tied together inside the module.

Power
Supply

4-Wire
Transmitter

Power
Supply

4-Wire
Transmitter

Connection Diagram for 16 Single-ended Inputs and Two-Wire Transmitters

Connection Diagram for 16 Single-ended Inputs and Four-Wire Transmitters

Field Wiring Arm

Field Wiring Arm

Functional Ground

single-ended wiring