Possible module fault causes and corrective action is described in the following
table.

Indicators

Probable Cause

Recommended Action

RUN (green on)

FLT (red off)

Normal operation

None

RUN (green blinking)

FLT (red off)

Awaiting configuration
block transfer write

Send configuration BTW

RUN (green off)

FLT (red on)

Hardware failure in
module

Return module for repair

RUN (green off)

FLT (red off)

No power

Turn off power. Remove and reinsert
module into chassis. Return power. If
problem still exists, and chassis
power supply is functioning properly,
return the module for repair.