Fast Analog Input Module 7

Set the Simulation Jumper

The module is shipped with the simulation jumper set in position POS G. This
setting allows input data to go above and below the range points. If the
simulation jumper is set to the POS E position, input data is clamped (does
not exceed) at range end points.

Set the Configuration
Jumpers

The module has configuration jumpers for determining the input type (voltage
or current) desired for each input. The module is shipped with the
configuration jumpers positioned for voltage mode.
Not that you can select either voltage or current for each input, but they must
all be either single-ended or all differential. Do not mix single-ended or
differential inputs on the module.

POS G

POS E

Simulation Jumper (shown in POS E
position). This position provides Clamped
Input Data at range end points.

Top edge of circuit board

1. Locate the simulation jumper at the top edge

of the module circuit board.

2. Using your fingers, slide the jumper of f the 2 posts.

3. Carefully position the jumper on 2 of the 3 posts that

correspond to your requirement.

Set the Simulation Jumper

Jumper

POS G

POS E

Simulation Jumper (shown in POS G
position). This position does not Clamp Input
Data at range end points.

Top edge of circuit board

Simulation

Simulation

Remove the four screws securing the side
cover to the module and remove the covers.

19805

11

Reposition the configuration jumpers associated with each
input channel according to your requirements

12

Y ou can mix voltage mode and current mode
settings on the module. Make sure that the entire
module is set for either single-ended or dif ferential.
Do not mix them.

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Channel 8

Channel
1 and 2
Channel
3 and 4

Channel
5 and 6

Channel
7 and 8

Channel
9 and 10

Channel
11 and 12

Channel
13 and 14

Channel
15 and 16

Differential

Single-ended

Voltage Mode

Differential

Current

Single-ended
Current

Differential or Single-ended (factory set)

Current Mode

Odd channel current

Even channel voltage

Even channel current

Odd channel voltage

Single-ended

Configuration
Jumpers

Reposition the cover and secure with the four
screws removed in step 1.