Fast Analog Input Module 13

Grounding

When using shielded cable wire, ground the foil shield and drain wire only at
one end of the cable. We recommend that you wrap the foil shield and drain
together, and connect them to a chassis mounting bolt, grounding stud or
chassis single-point grounding point. Use heat-shrink tubing to seal the exit
point of the wires. At the opposite end of the cable, tape exposed shield and
drain wire with electrical tape to insulate it from electrical contact.

Remove a length of cable
jacket from the Belden 8761
cable.

Pull the foil shield and bare
drain wire from the insulated
wires.

Bare drain
wire

Insulated
wires

Foil
shield

Twist the foil shield and drain
wire together to form a single
strand.

Attach a ground lug, and apply
heat shrink tubing to the exit area.

20104

Belden 8761 Cable

Length as needed

Cable Grounding

1

19480

Grounding Stud

1

Use the cup washer if crimp-on lugs are not used.

Chassis Ground

Ground Lug

Ground Lug

1

Star
Washer

I/O Chassis
Side Plate

Nut and Captive
Washer

External-tooth
Washers

#10 Thread-forming screw

19923

Shield and Drain
twisted together

Shield and Drain
twisted together

Single-point Grounding

Extend shield to termination point. Expose just enough
cable to adequately terminate inner conductors.

Use heat shrink tubing or
other suitable insulation
where wire exits cable
jacket.

Nut

When you connect grounding conductors to the I/O
chassis grounding stud, place a star washer under the
first lug, then place a nut with captive lock washer on
top of each ground lug.

2