4 Fast Analog Input Module

North American Hazardous Location Approval

This 1771-IFF series A module is hazardous location approved.

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l’utilisation de cet
équipement en environnements dangereux :

Products marked “CL I, DIV 2, GP A, B, C, D” are
suitable for use in Class I Division 2 Groups A,
B, C, D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with
markings on the rating nameplate indicating the
hazardous location temperature code. When
combining products within a system, the most
adverse temperature code (lowest “T” number)
may be used to help determine the overall
temperature code of the system. Combinations
of equipment in your system are subject to
investigation by the local Authority Having
Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D"
ne conviennent qu’à une utilisation en
environnements de Classe I Division 2 Groupes A,
B, C, D dangereux et non dangereux. Chaque
produit est livré avec des marquages sur sa
plaque d’identification qui indiquent le code de
température pour les environnements dangereux.
Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus
défavorable (code de température le plus faible)
peut être utilisé pour déterminer le code de
température global du système. Les
combinaisons d’équipements dans le système
sont sujettes à inspection par les autorités
locales qualifiées au moment de l’installation.

EXPLOSION HAZARD

Do not disconnect

equipment unless power has
been removed or the area is
known to be nonhazardous.

Do not disconnect

connections to this equipment
unless power has been
removed or the area is known
to be nonhazardous. Secure
any external connections that
mate to this equipment by
using screws, sliding latches,
threaded connectors, or other
means provided with this
product.

Substitution of components

may impair suitability for
Class I, Division 2.

If this product contains

batteries, they must only be
changed in an area known to
be nonhazardous.

RISQUE D’EXPLOSION

Couper le courant ou s’assurer

que l’environnement est classé
non dangereux avant de
débrancher l'équipement.

Couper le courant ou s'assurer

que l’environnement est classé
non dangereux avant de
débrancher les connecteurs.
Fixer tous les connecteurs
externes reliés à cet équipement
à l'aide de vis, loquets
coulissants, connecteurs filetés
ou autres moyens fournis avec
ce produit.

La substitution de composants

peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.

S’assurer que l’environnement

est classé non dangereux avant
de changer les piles.