Communicate with your armorblock module – Rockwell Automation 1792-IB8/B INSTL.INST ARMOR BLOCK 8 INPUT User Manual

Page 10

Advertising
background image

ArmorBlock 8 Input Module

10

Publication 1792-5.2 – October 1996

Communicate with Your ArmorBlock Module

This ArmorBlock module acts as a slave in a master/slave environment.
It is both a “polled device” and a “change of state device.”

When configured as a polled device, a master initiates communication
by sending its polled I/O message to the ArmorBlock module. The 8
input module scans the inputs and fault bit producing a response that
reflects their status.

When configured as a “change of state” device, productions occur
when an input changes or an input source voltage fault occurs. If
neither has occurred within the “expected packet rate,” a heartbeat
production occurs. This heartbeat production tells the scanner module
that the ArmorBlock module is alive and ready to communicate.

Bit

07

06

05

04

03

02

01

00

Produces

I7

I6

I5

I4

I3

I2

I1

I0

Produces

S

Reserved

Where: I = Input

S = Sensor source voltage fault

Word

Bit

Description

Produces

1

00–07

Input bits – bit 00 corresponds to input 0, bit 01 to input 1, and
so on.
0 = input off; 1 = the input is on.

Produces

00–06

Reserved

2

07

Sensor source voltage fault bit – this bit is set (1) when the sensor
source voltage is faulted.