Troubleshoot with the indicators, Mod/net status indicator, Input fault indicator – Rockwell Automation 1792-IB8/B INSTL.INST ARMOR BLOCK 8 INPUT User Manual

Page 34: Individual i/o status indicators

Advertising
background image

ArmorBlock 8 Input Module

34

Publication 1792-5.2 – October 1996

Troubleshoot with the Indicators

The ArmorBlock I/O module has 3 types of indicators:

Mod/Net status indicator

Input fault indicator

individual I/O status indicators

Input I/O Status Indicators

Mod/Net Status Indicator

Input Fault Indicator

MOD/NET

STATUS

INPUT
FAULT

NODE

ADDRESS

DA

TA

RA

TE

ARMORBLOCK I/O

1792-IB8

Note:

This module contains a circuit to protect the DeviceNet power supply from short circuits
in an attached sensor or sensor cable. If you connect a sensor while the module is
powered, the surge current produced by the sensor can cause the module to fault. This
operation is normal. If this occurs, reset the module (page 25).

Mod/Net Status Indicator

Indication

Status

OFF

No power, or no network access, or incorrect baud rate

1

Flashing Green/OFF

On-line but not connected

Solid Green

On-line, link okay, connected

Flashing Red

Recoverable fault

Solid Red

Critical failure, or duplicate node address present

Green to Red to Off

At powerup only – The module is autobauding

1

This only occurs when Autobaud is disabled, and the module is set to an incorrect baud rate.

Input Fault Indicator

Indication

Status

OFF

Sensor source voltage operating correctly

Solid Red

1 or more Sensor source voltage shorts

Input I/O Status Indicator

Indication

Status

OFF

No valid input signal present

Yellow

Valid input signal present