Specifications – Rockwell Automation 1792-IB8/B INSTL.INST ARMOR BLOCK 8 INPUT User Manual

Page 35

Advertising
background image

35

ArmorBlock 8 Input Module

Publication 1792-5.2 – October 1996

Specifications

8 Input Module – Cat. No. 1792-IB8

Input Specifications

Inputs per Block

8 sinking

On-state Voltage Range

10–30V dc

On-state Current

Maximum
Minimum

6.0mA @ 30V dc
2.0mA @ 10V dc

Off-state Voltage

Maximum

5V dc

Off-state Current

Minimum

1.5mA

Transition Voltage

5–10V dc

Transition Current

1.5–3.0mA

Input Impedance

Maximum

5K ohms

Input Signal Delay

Off to On
On to Off

0ms, 2ms, 4ms, 8ms, 16ms
0ms, 2ms, 4ms, 8ms, 16ms

Sensor Source

Voltage
Current

10–25V dc
50mA per point, 0.4A total per module

Indicators

Mod/Net Status – red/green
Input Fault – red
I/O Status – yellow (customer field side driven)

General Specifications

DeviceNet Power

Voltage
Current

11.0 – 25.0V dc
100mA (no powered sensors)
500mA (full sensor load)

Surge Current at Power Up

Less than 10A for 5ms

Dimensions

Inches
Millimeters

2.6H X 7.7W X 3.06D
66H X 195W X 77.7D

Connectors

1792-IB8A/B – Aluminum connectors
1792-IB8S/B – Stainless Steel Connectors

Power Dissipation

Maximum

1.9 Watts

Thermal Dissipation Maximum

6.5 BTU/hr

Specifications continued on next page.