Introducing Block I/O

Chapter 1

1-5

In sourcing input modules (Figure 1.4), the +V on dc circuits is bussed on
the module supplying (sourcing) the current for each input circuit. The
field device switches the circuit to the common (side of the power supply,
sinking the circuit and causing current to flow from the module’s input.

Figure 1.4
Sourcing Input Example

Field
Device

Input

+V

10917-I

Block I/O

DC Power
Supply

dc Common Bus

-V

In sinking outputs (Figure 1.5), the current flow is reversed. The dc
common is bussed on the module and the current is sourced from the field
device being actuated. When an output is turned on, the output switch in
the module sinks the circuit, causing current to flow from the +V bus
through the field device to the module.

Note: The outputs must be externally fused to protect the device output
against overcurrent or short circuit conditions.

Figure 1.5
Sinking Output Example

DC Power
Supply

Field
Device

Field
Device

+V

-V

Bus

Common

Fuse

Fuse

10918-I

Block I/O

Common