Rockwell Automation 1791-I0VX BLOCK I/O User Manual

Page 27

Advertising
background image

Installing Block I/O

Chapter 2

2-15

Certain products are not compatible with extended node capabilities
obtained with the use of 82 ohm terminators. The following table lists
those products that are not compatible.

Device

Series

Scanners -1771-SN

All

1772-SD

All

1772-SD2

All

1775-SR

1

All

1775-S4A

1

All

1775-S4B

1

All

Adapters -

1771-AS

All

1771-ASB

Series A

1771-DCM

All

Miscellaneous -

1771-AF

All

1771-AF1

All

1

When using PLC-3 programmable controllers, you must use a
1775-S5 or -SR5 scanner module. Do not use 1775-SR, -S4A
or -S4B scanner modules.

1791 high-density block I/O modules (64 and 128 input/output) have
internal fusing. Each group of 16 output points is protected by a 5.0A fuse.
These fuses protect the user output devices. They do not protect each
individual output from overload. It is recommended that individual outputs
be fused externally to protect the individual output circuit.

Catalog Number

Voltage

Maximum Output Rating at:

30

o

C 60

o

C

Maximum Surge Current

1791-IOBX

24V dc

300mA per point

2.4A continuous per 16 point group

1 0A

25

1791-IOVX

24V dc

2.4A continuous per 16 point group

maximum surge current 1.0A for 25ms

1 pulse per second maximum

Consult the factory for fuse recommendations.

In this chapter you learned how to physically mount your block I/O, make
power wiring connections, how to make the input/output wiring
connections to the block, and how to terminate the remote I/O link.

Compatibility of 1771 I/O
Products with Extended
Node Operation

Fusing

Summary