Specifications – Rockwell Automation 1791-I0VX BLOCK I/O User Manual

Page 47

Advertising
background image

Appendix

A

A-1

Specifications

General Specifications

External power

Range: 18 to 26.4V dc
300mA @ 24V dc; initial surge 2.0A for 10msec

Power Dissipation

25.2 Watts (maximum); 15.2 Watts (typical)

Thermal Dissipation

86.2 BTU/hr (maximum); 51.9 BTU/hr (typical)

Remote I/O Isolation

850V dc (transformer) for 1 second

Interconnect cable length
PLC or SLC

RIO:

57.6K

10,000 cable–feet

115.2K

5,000 cable–feet

230.4K

2,500 cable–feet

Cable requirements

RIO – Belden 9463

Dimensions

Inches:

6.15W x 13.0H x 1.72D

Millimeters:

156.21W x 334.0H x 43.7D

Conductors

Wire Size

Category

14 gauge (2mm

2

) stranded (maximum)

3/64 inch (1.2mm) insulation (maximum)
2

1

Environmental Conditions

Operating Temperature
Storage Temperature
Relative Humidity

Operating
Non-operating

32 to 140

o

F (0 to 60

o

C)

–40 to 185

o

F (–40 to 85

o

C)

5 to 95% noncondensing
5 to 80% noncondensing

1

Refer to publication 1770–4.1, Programmable Controller Wiring and Grounding Guidelines

Input Specifications

Number of Inputs

64 (4 groups of 16)

Input type

1791–IOBX – Sinking; 1791–IOVX – Sourcing

On-state voltage range

12.0 to 26.4V dc

On–state input current

1.56mA (minimum)

Off–state voltage

7.0V dc (maximum)

Off–state current

1.0mA dc (maximum)

Turn On time

10msec (maximum) (+4msec)

Turn Off time

10msec (maximum) (+4msec)

Input to System Isolation

1500V ac (opto) for 1 second

Group to Group Isolation

1500V ac (air gap) for 1 second

Advertising
This manual is related to the following products: