Installing Block I/O

Chapter 2

2-12

Power Supply Requirements

An external 24V dc (+10/-25%) power supply is required to power the
block. Total current required to power the block is equal to 300mA.

In addition, the external power supply should have current limiting
capabilities. The voltage range must not exceed 18.0-26.4V dc.

Wiring Requirements

Wiring cable requirements are shown in Table 2.J.

Table 2.J
Acceptable Wiring Cables for Block I/O Connection

Use

Cable Type

With

Remote I/O Link

Belden 9463

PLC-2, PLC-3, PLC-5 family programmable
controllers and SLC controllers

Input and Output wiring

Up to 14AWG (2mm

2)

Stranded

with 3/64 inch (1.2mm) insulation

All

Figure 2.3
Remote I/O Link Wiring

GROUP No.

GROUP No.

2

(CLR)

Shield

1

(BLU)

24VDC

RET

24VDC

Connection

Clear wire X

Blue wire X

Shield wire X

Chassis

GND

2

(CLR)

1

(BLU)

Shield

10928-I

- 150 OHM

- 82 OHM

-OFF

TERMINATION
RESISTOR