Configuring Your Block I/O

Chapter 3

3-5

Rack Address Switch Position

PLC-3

Rack

Number

PLC-5/250

Rack

Number

PLC-5

Rack

Number

PLC-2

Rack

Number

1771-SN

Rack

Number

1747-SN

Rack

Number

1

2

3

4

5

6

PLC-3

Rack

Number

PLC-5/250

Rack

Number

PLC-5

Rack

Number

PLC-2

Rack

Number

1771-SN

Rack

Number

1747-SN

Rack

Number

Rack 63

1

1

0

0

1

1

Rack 64

1

1

0

1

0

0

Rack 65

1

1

0

1

0

1

Rack 66

1

1

0

1

1

0

Rack 67

1

1

0

1

1

1

Rack 70

1

1

1

0

0

0

Rack 71

1

1

1

0

0

1

Rack 72

1

1

1

0

1

0

Rack 73

1

1

1

0

1

1

Rack 74

1

1

1

1

0

0

Rack 75

1

1

1

1

0

1

Rack 76

1

1

1

1

1

0

Not Valid

1

1

1

1

1

1

Rack address 77 is an illegal configuration.
PLC-5/11 processors can scan rack 03.
PLC-5/15 and PLC-5/20 processors can scan racks 01-03.
PLC-5/25 and PLC-5/30 processors can scan racks 01-07.
PLC-5/40 and PLC-5/40L processors can scan racks 01-17.
PLC-5/60 and PLC-5/60L processors can scan racks 01-27.
PLC-5/250 processors can scan racks 00-37.
PLC-3 processors can scan racks 00-76.

Each block uses 4 words of output image table memory and 4 words of
input image table memory. Each block occupies 1/2 rack of data table, with
2 blocks comprising 1 logical rack. Image table usage for one assigned
rack number is shown in Figure 3.3. An example of image table usage is
shown in Figure 3.4.

Figure 3.3
I/O Image Table for One Assigned Rack Number

0

17

Output Image

Input Image

0
1
2
3
4
5
6
7

7

10

0

17

0
1
2
3
4
5
6
7

7

10

1791-IOVX

1791-IOBX

Rack 1

2 1791-IOBX or 1791-IOVX per rack
1st 1/2 rack = module group 0-3
2nd 1/2 rack = module group 4-7

Block 1

Inputs

Block 2

Inputs

Block 1

Outputs

Block 2

Outputs

1

2

10933-I