Input size – Rockwell Automation 1761-NET-DNI DeviceNet Interface (DNI) User Manual
Page 29

Publication 1761-UM005B-EN-P - October 2006
DNI Configuration Parameters and Programming Notes 29
Input Size
This parameter identifies the size, in words, of the data array that is
read from the controller attached to the DNI’s RS-232 port.
The array may contain up to 16 (16-bit) words of data for DNI Series A
(32 words for DNI Series B) from a contiguous block within the
attached controller.
Messaging
2
15
Message Timeout
0…2500 ms
0 ms
Messaging
Not
Applicable
16
DF1 Substitute
Address
0…64
64 = Disabled
DF1
15
17
DF1 Autobaud
Disabled (0) or
Enabled (1)
Enabled (1)
DF1
16
18
DF1 Baud Rate
0…5:
0: 38,400
1: 19,200
2: 9600
3: 4800
4: 2400
5: 1200
Series A: 2 = 9600
Series B: 1 = 19,200
DeviceNet
1
19
DeviceNet Autobaud Disabled (0) or
Enabled (1)
Enabled (1)
Device
17
Not
Applicable
DNI Mode
Standby (0) or
Operational (1)
Operational (1)
EDS Parameters for the DNI
Input Size Parameter Definition
Parameter
Type
Parameter Number Description
Range
Default
Value
Series
A
Series B
I/O
4
1
Input Size
Series A: 1…16
Series B: 1…32
1
IMPORTANT
For DNI Series B, you must also configure the Input
Split Point.
See Input Split Point on page 30.