Example dni configuration parameters – Rockwell Automation 1761-NET-DNI DeviceNet Interface (DNI) User Manual
Page 70

Publication 1761-UM005B-EN-P - October 2006
70 Application Examples
Example DNI Configuration
Parameters
All example ladder logic programs in this section use the following
DNI configuration.
Parameter Number
Description
Range
Default Value
For this Example,
ENTER
Series A
Series B
4
1
Input Size
Series A: 1…16
Series B: 1…32
1 word
4 words
Not
Applicable
2
Input Split Point
1…32
1 word
4 words
5
3
Input Type
Bit or Integer File
Integer File
Integer File
6
4
Input Data File
3…254
7
7
7
5
Input Word Offset
0…254
0
90
8
6
Output Size
Series A: 1…16
Series B: 1…32
1 word
4 words
Not
Applicable
7
Output Split Point
1…32
1 word
4 words
9
8
Output Type
Bit or Integer File
Integer File
Integer File
10
9
Output Data File
3…254
7
7
11
10
Output Word Offset
0…254
1
95
14
11
DF1 Device
0…3:
0: Other
1: PLC
2: SLC/ Other MicroLogix
3: MicroLogix 1000
3 = MicroLogix 1000
3 = MicroLogix 1000
3
12
DNI Series A:
Data Enable
DNI Series B:
I/O Scan Enable
(Polling Enable)
0 or 1
Disabled (0)
Enabled (1)
12
13
DF1 Heartbeat
Series A: 2…10
Series B: 1…10
2
2
13
14
Data Scan Delay
(Polling Delay)
20…3000 ms
50 ms
100 ms
2
15
Message Timeout
0…2500 ms
0 ms
0 ms
Not
Applicable
16
DF1 Substitute
Address
0…64
64 = Disabled
64 = Disabled
15
17
DF1 Autobaud
Disabled (0) or Enabled (1) Enabled (1)
Enabled (1)