34 DNI Configuration Parameters and Programming Notes
Input Word Offset
This parameter identifies the starting word within the input file
identified by the parameter Input Data File. The value entered is the
first word of data that is read from the controller attached to the DNI.
The sizes of compatible data files within Allen-Bradley controllers vary
based on the DFI device selected.
Parameter
Type
Parameter Number
Description
Range
Default Value
Series A
Series B
I/O
7
5
Input Word Offset
0…254
0
Compatible Data File Sizes
Controller
Input Data Files
File Size
MicroLogix 1000
Bit
32 Words
Integer
105 Words
SLC/Other MicroLogix
Bit
255 Words
Integer
255 Words
PLC
Bit
999 Words
Integer
999 Words
TIP
The DNI can only access files 3 through 254.
IMPORTANT
You must have sufficient room in the file that you
select. Make sure the Input Word Offset plus the
Input Size does not exceed the boundary of the
controller’s data file. For example, a MicroLogix 1000
controller has 32 words in its bit file; therefore, you
could not use a Input Word Offset of 30 and a Input
Size of 5 because this exceeds the file size.