I/o memory mapping, Output data file, Addressing – Rockwell Automation 1762-OA8 Solid State Output Module User Manual
Page 10: O0:x.0/0
Advertising
10 Solid-State Output Module
Publication 1762-IN007B-EN-P- June 2013
I/O Memory Mapping
Output Data File
For each output module, the output data file contains the controller-directed state of the discrete
output points. Bit positions 0…7 correspond to output terminals 0…7.
w = write only, 0 = always at a 0 or OFF state
Addressing
The addressing scheme for 1762 Expansion I/O is shown below.
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with
slot 1.
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
w
w
w
w
w
w
w
w
O0:x.0/0
Output
Data File
Slot Number
(1)
Word (always zero for this module)
Bit (0…7)
Bit Delimiter
Word Delimiter
Slot Delimiter