12 Solid-State Output Module

Publication 1762-IN007B-EN-P- June 2013

Output Specifications

Turn On Type

- Triac outputs turn on at ac line zero cross, and off at zero current.

Recommended Loading Resistor

- to limit the effects of leakage current through solid-state

outputs, a loading resistor can be connected in parallel with your load. For 120V AC operation,
use a 15k

Ω, 2W resistor. For 240V AC operation, use a 15k Ω, 5W resistor.

Surge Suppression

- Connecting surge suppressors across your inductive loads reduces the stress

on your triac outputs. This also helps minimize the load-induced electromagnetic emissions that
are conducted on your plant wiring. For 120V loads, we recommend the Littelfuse-Harris surge
suppressor, part number V175LA10A MOV or an equivalent device. For 240V loads, we
recommend the Littelfuse-Harris surge suppressor, part number V250LA20A MOV or an
equivalent device.

Specification

Value

Voltage Category

100…240V AC

Operating Voltage Range

85…265V AC @ 47…63 Hz

Number of Outputs

8

Bus Current Draw, max

115 mA @ 5V DC (0.575W)

Heat Dissipation, max

2.9 Total Watts

Signal Delay, max (resistive load)

On Delay: 1/2 cycle

Off Delay: 1/2 cycle

Off-State Leakage, max

2 mA @ 132V, 2.5 mA @ 265V

On-State Current, min

10 mA

Continuous Current per Point, max

0.25 A @ 55 °C; 0.5A @ 30 °C

Continuous Current per Common, max 1.0 A @ 55 °C; 2.0 A @ 30 °C

Continuous Current per Module,max

2.0 A @ 55 °C; 4.0 A @ 30 °C

Power Supply Distance Rating

6

Isolated Groups

Group 1: Outputs 0…3

Group 2: Outputs 4…7

Output Group to Backplane Isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or
2596V DC for 1 s

265V AC working voltage (IEC Class 2 reinforced insulation)

Output Group to Output Group
Isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or
2596V DC for 1 s

265V AC working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. Code

1

Product Type Code

7

Product Code

119

On-State Voltage Drop, max

1.5V @ 0.5 A

Surge Current, maximum

5.0 A (Repeatability is once every 2 s for a duration of 25 ms)