14 Solid-State Output Module

Publication 1762-IN007B-EN-P- June 2013

North American Hazardous Location Approval

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous
locations only.

The following WARNING statement applies to use in hazardous locations.

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l’utilisation de cet équipement
en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C, D,
Hazardous Locations and nonhazardous locations only.
Each product is supplied with markings on the rating
nameplate indicating the hazardous location
temperature code. When combining products within a
system, the most adverse temperature code (lowest
"T" number) may be used to help determine the overall
temperature code of the system. Combinations of
equipment in your system are subject to investigation
by the local Authority Having Jurisdiction at the time
of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l'installation.

WARNING

EXPLOSION HAZARD

• Substitution of components may impair

suitability for Class I, Division 2.

• Do not replace components or disconnect

equipment unless power has been
switched off.

• Do not connect or disconnect components

unless power has been switched off.

• This product must be installed in an

enclosure.

• In Class I, Division 2 applications, the bus

connector must be fully seated and the
bus connector cover must be snapped in
place.

• In Class I, Division 2 applications, all

modules must be mounted in direct
contact with each other as shown on
Page 6. If DIN rail mounting is used, an
end stop must be installed ahead of the
controller and after the last 1762 I/O
module.

• All wiring must comply with N.E.C. article

501-4(b).

• The interior of the enclosure must be

accessible only by the use of a tool.

• For applicable equipment (relay modules,

etc.), exposure to some chemicals may
degrade the sealing properties of
materials used in the following devices:
Relays, Epoxy. It is recommended that the
User periodically inspect these devices for
any degradation of properties and replace
the module if degradation is found.

AVERTISSEMENT

RISQUE D’EXPLOSION

• La substitution de composants peut rendre

cet équipement impropre à une utilisation
en environnement de Classe 1, Division 2.

• Ne pas remplacer de composants ou

déconnecter l'équipement sans s'être
assuré que l'alimentation est coupée.

• Ne pas connecter ou déconnecter des

composants sans s'être assuré que
l'alimentation est coupée.

• Ce produit doit être installé dans une

armoire.

• Pour les applications de Classe I, Division 2,

le connecteur de bus doit être correctement
installé et son couvercle enclenché.

• Pour les applications de Classe 1, Division

2, tous les modules doivent être installés en
contact direct les uns avec les autres,
comme indiqué page 6. Si on utilise le
montage sur rail DIN, une butée doit être
placée à l'avant de l'automate et après la
dernière unité d'E/S 1762.