Selecting Options

Chapter 3

3Ć6

Switch

I/O Rack Number (Octal)

1

2

3

4

5

6

30

ON

OFF

OFF

ON

ON

ON

31

ON

OFF

OFF

ON

ON

OFF

32

ON

OFF

OFF

ON

OFF

ON

33

ON

OFF

OFF

ON

OFF

OFF

34

ON

OFF

OFF

OFF

ON

ON

35

ON

OFF

OFF

OFF

ON

OFF

36

ON

OFF

OFF

OFF

OFF

ON

37

ON

OFF

OFF

OFF

OFF

OFF

Switches 7 and 8 Ć First (Starting) Module Group Number

First Module

Switch

Group Number

7

8

0

ON

ON

2

ON

OFF

4

ON

ON

6

OFF

OFF

Assign a unique stating module group number--such as 0, 2, 4, or 6--in
accordance with the number of chassis you assigned to the same I/O rack
number. You can assign from one to four 1771-DCMs and I/O adapters to
the same I/O rack number, provided that the combination does not exceed
a full rack. For example, assign starting module group numbers to each
I/O chassis or 1771-DCM in the following combinations:

Rack Configuration

Assign Module Group Numbers

Four 1/4 Racks

0, 2, 4, and 6

Two 1/2 Racks

0 and 4

One 1/4 and One 3/4 Rack

0 and 2

One 3/4 and One 1/4 Rack

0 and 6

You selected the equivalent rack size of your 1771-DCM with Switch
Bank 0, Switches 7 and 8, above.