Programming the 1771-DCM

Chapter 6

6Ć4

First (Starting) Module Group Number (Switch Bank 1, Switches 7 and

8)

The slot number will always be zero for block transfer only.
Equivalent rack size for discrete data transfer only (Switch Bank 0,

Switches 7 and 8). The equivalent rack size for block transfer mode is
fixed at 1/4 rack.

Discrete Data Transfer

The supervisory processor transfers discrete data to and from the
1771–DCM automatically via its I/O scan. You do not program these
transfers.

To transfer discrete data words to and from the 1771–DCM, you must use
I/O image table addresses in the supervisory processor’s ladder program
starting with the addresses (RGS) to which you configured your
1771–DCM. Use the number of image table words equal to the
equivalent I/O rack size that you set for the 1771–DCM.

The ladder program of your supervisory processor must move discrete
data, read from the 1771–DCM, from input image table words to a storage
location (Figure 6.3).

Figure 6.3

Supervisory Processor Programming Example for Discrete Data Transfer (PLC-2/30)

EN

FILE TO FILE MOVE

Counter Address:

Position:

File Length:

File A:

0041

001

008

0120-0127

File R:

0700-0707

Rate per Scan:

008

0041

17

DN

0041

15

15

041

10

120

Buffer File

Data Valid Bit

FFM Done Bit

Your ladder program must place data into output image table words for
transfer to the 1771–DCM. Avoid placing data in the first word because
the 1771–DCM inserts status in this word. We leave this ladder logic to
you because your application and processor’s set of instructions determine
how you would do this.