Rockwell Automation 1771-DCM USER MANUAL 1771-DCM User Manual

Page 37

Advertising
background image

Calculating Transfer Time

Chapter 7

7Ć3

Processor

Multiplier

PLCĆ2/05, Ć2/15

0.08

PLCĆ2/30 (Local)

0.08

PLCĆ2 Family Example Computation

Suppose that a PLC-2/30 supervisory processor has a 6K program and
seven assigned rack numbers and the PLC-2/05 local processor has a 2K
program. There are no other block transfer modules in either the
supervisory or local systems.

1.

Calculate the time required to transfer eight words from supervisory
to local processor.

2.

Calculate the total time required if there are two additional block
transfer modules in the local chassis, transferring 64 words each.
Assume worst case.

Solution Part 1:

PLC-2/30 Supervisory Processor Scan Time:

Scan

PLCĆ2/30

Program

5 ms/K Words

Processor I/O

0.5 ms/Rack

Remote I/O

7 ms/Chassis

Time (PLC-2/30) = Program + Processor I/O + Remote I/O

= (5 ms)(6) + (0.5 ms)(7) + (7 ms)(7)
= 30 ms + 3.5 ms + 49 ms
= 82.5 ms

1771-DCM Delay: 15 ms

Local Processor Scan Time:

Time for

PLCĆ2/05

I/O Scan

1 ms

Program Scan

15 ms/K

Block Transfer

0.08 ms/W

Advertising