Using the Status Word

Chapter 5

5Ć3

Bit 14 Ć Not Used

Bit 13 Ć No Data Available

Set by the 1771-DCM at power-up. The 1771-DCM rests this bit when it
receives data from the supervisory processor.

Bit 12 Ć Not Used

Bit 11 Ć Inhibit Outputs

Set by the 1771-DCM to inform the local processor that the supervisory
processor has been switched to program or test mode, has switched itself
to program mode because of a dependent I/O fault (PLC-2 family), or that
the 1771-DCM has lost communication with the supervisory processor.

Bit 10 Ć Invalid Data

Set by the 1771-DCM whenever it sets any other status bit. As long as
this bit is reset, the 1771-DCM has detected no error condition or change
in status.

When the 1771-DCM detects an error in its communication with the local
processor, it indicates this condition in the status word read by the
supervisory processor as follows:

17

16

15

14

13

12

11

10

Insuf

Excess

Backplane

Backplane

No

Old

0

Invalid

Data

Data

Reset

Error

Data

Data

Data

Bits 17, 16, 13, and 10 Ć Same as Local Processor

Bit 15 Ć Backplane Reset

Set by the 1771-DCM to inform the supervisory processor that the local
processor has reset the backplane. The local processor typically resets the
backplane when switched to program/test mode, or when it detects a fault
condition and turns off outputs. The 1771-DCM cannot detect a
backplane reset due to a fault condition resulting in outputs remaining in
last state. You determine the last state condition (hold last state or turn
off) by a DIP switch on the I/O chassis.