Programming the 1771-DCM

Chapter 6

6Ć12

Example 2:

Suppose you want to transfer 64 words, and you have configured the
1771–DCM to simulate a block transfer module in Rack 2, First
Module Group = 0. Also suppose that the 1771–DCM is located in
the same chassis with the local processor, and that the 1771–DCM’s
actual location (RGS) is 131. In this example, you allocated data
blocks for block transfer as follows: (Refer to Figure 6.4 for
PLC–2/30, or Figure 6.5 for PLC–3 Programming)

Data Block

Supervisory Processor

Local Processor

Read

600 through 677

300 through 377

Write

500 through 577

200 through 277

Data transfers would occur as follows for PLC–2 family processors:

Supervisory Processor To Local Processor

BTW Instruction Writes Data to the

1771-DCM from Words 500 through

577

BTR Instruction Reads Data from the

1771-DCM into Words 300 through 377

500 Status Word (Zeroed)

501 First Data Word

502 Second Data Word

:

:

577 Last Data Word

300 Status Word (Inserted by DCM)

301 First Data Word

302 Second Data Word

:

:

377 Last Data Word

Local Processor To Supervisory Processor

BTW Instruction Writes Data to the

1771-DCM from Words 200 through

277

BTR Instruction Reads Data from the

1771-DCM into Words 600 through 677

200 Status Word (Zeroed)

201 First Data Word

202 Second Data Word

:

:

277 Last Data Word

600 Status Word (Inserted by DCM)

601 First Data Word

602 Second Data Word

:

:

677 Last Data Word