Chapter 2 Manage event tasks

To trigger an event task when

Use this trigger

With these considerations

Motion planner completes its execution

Motion Group Execution

The base update period for the motion group triggers both the motion planner and the event

task.

Because the motion planner interrupts all other tasks, it runs first. If you assign the event task as

the highest priority task, it runs after the motion planner.

Specific condition or conditions occur within

the logic of a program

EVENT instruction

Multiple EVENT instructions can trigger the same task. This lets you run a task from different

programs.

The following table lists some example situations for event tasks and the

corresponding triggers.

For this example situation

Use an event task with this trigger

A packaging line glues boxes closed. When a box arrives at the gluing position, the controller must immediately run the

gluing routine.

Module Input Data State Change

A production line uses a proximity sensor to detect the presence of a part. Because the proximity sensor is on for only a very
short time (pulse), the continuous task might miss the off to on transition of the sensor.

Module Input Data State Change

In an engine test stand, you must capture and archive each sample of analog data.

Module Input Data State Change

Controller A produces an array of production data for Controller B. You want to make sure that Controller B doesn’t use the
values while Controller A is updating the array.

Consumed Tag

In a line that packages candy bars, make sure that the perforation occurs in the correct location on each bar. Each time the
registration sensor detects the registration mark, check the accuracy of an axis and perform any required adjustment.

Axis Registration 1 or 2

At the labeling station of a bottling line, you want to check the position of the label on the bottle. When the axis reaches the

position that is defined as the watch point, check the label.

Axis Watch

A gluing station must adjust the amount of glue it applies to compensate for changes in the speed of the axis. After the
motion planner runs, check the command speed of the axis and vary the amount of glue, if needed.

Motion Group Execution

In a production line, if any of the programs detect an unsafe condition the entire line must shut down. The shutdown
procedure is the same regardless of the unsafe condition.

EVENT instruction

The triggers that you can use for an event task vary by your controller type.

Important: The Logix Designer application may let you configure a trigger for an event task that your controller does

not support. The project verifies and successfully downloads, but the event task does not run.

If You Have This
Controller

Then Use These Event Task Triggers

Module Input Data
State Change

Consumed Tag Axis Registration

1 or 2

Axis Watch

Motion Group
Execution

EVENT
instruction

CompactLogix

X

X

FlexLogix

X

X

ControlLogix

X

X

X

X

X

X

DriveLogix

X

X

X

X

X

SoftLogix5800

X

1

X

2

X

X

X

X

(1) Requires a 1756 I/O module or a virtual backplane.

(2) A SoftLogix5800 controller produces and consumes tags only over a ControlNet network.

36

Rockwell Automation Publication 1756-PM005-EN-P - October 2014