Chapter 2 Manage event tasks

The following table lists nominal hardware response times for 1756 I/O modules

with event tasks.

Cat. No.

Nominal response time µs
25 °C

60 °C

Off On

On Off

Off On

On Off

1756-IB16

265

582

265

638

1756-IB16D

303

613

305

673

1756-IB32/B

330

359

345

378

1756-IV16

257

435

254

489

1756-IV32

381

476

319

536

1756-OB16D

48

519

51

573

1756-OB16E

60

290

61

324

1756-OB32

38

160

49

179

1756-OV16E

67

260

65

326

1756-OV32E

65

174

66

210

Example – estimate throughput

The following example shows the throughput considerations for the system shown

in the following illustration. In this example, the throughput is the time from

when the input turns on to when the output turns on.

44

Rockwell Automation Publication 1756-PM005-EN-P - October 2014