Chapter 2 Manage event tasks

Make sure your module can trigger an event task

To use an input module to trigger an event task, the module must support event

task triggering. If the module is in a remote location, the associated

communication modules must also support event triggering.

The following table lists Rockwell Automation modules that have been tested for

event task triggering. Some third-party modules may also support event task

triggering. Before you use a third-party module, check with the supplier to validate

the operation of the module.

Category

Modules

Digital I/O modules that support change of state

1756-IA8D
1756-IA16I
1756-IB16
1756-IB16I
1756-IB32
1756-IG16
1756-IH16ISOE
1756-IN16
1756-IV32

1756-IA16
1756-IA32
1756-IB16D
1756-IB16ISOE
1756-IC16
1756-IH16I
1756-IM16I
1756-IV16

Analog I/O modules that support real time sample

1756-IF16
1756-IF6CIS
1756-IF8
1756-IT6I

1756-IF4FXOF2F/A
1756-IF6I
1756-IR6I
1756-IT6I2

Communication modules that provide rack-optimized

connections

1756-CNB/A
1756-CNB/D
1756-CNBR/B
1756-DNB
1756-SYNCH/A

1756-CNB/B
1756-CNBR/A
1756-CNBR/D
1756-ENBT/A
1784-PCIDS/A

Generic I/O modules that conform to CIP event
communication

1756-MODULE
1789-MODULE

Checklist for an Input Event Task

Use the following checklist when creating an Input Event Task.

For This

Make Sure You

1. Input module type

For the fastest response, use these modules:

For fastest digital response, use a 1756-IB32/B module.

For fastest analog response, use a 1756-IF4FXOF2F module.

2. I/O module location

Place the module that triggers the event and the modules that respond to the event (outputs) in the same chassis as the controller.
Remote modules add network communication to the response time.

3. Number of local modules

Limit the number of modules in the local chassis.
Additional modules increase the potential for backplane delays.

40

Rockwell Automation Publication 1756-PM005-EN-P - October 2014

Advertising