Interpreting the status indicators troubleshooting – Rockwell Automation 1771-OAD AC(12-120V)Output Installation Instructions User Manual

Page 11

Advertising
background image

AC (12-120V) Output Module

11

Publication 1771ĆIN024B-EN-P - November 2002

The front panel has one green module active indicator, 16 red status
indicators, and one red fuse-blown indicator.

ACTIVE

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

Module Active

Indicator (green)

00 to 17 Status

Indicators (red)

FUSE

Fuse Blown

Indicator (red)

12225-I

Indicator

Mode

Description

Active

Standard Mode

(STD)

The active indicator lights when the rack power supply has properly

established5V dc andthe processor is in RUN mode.

Customer Side

Indication (CSI)

The active indicator lights when the rack power supply has properly

established5V dc.

Status

STD or CSI

The status indicators light when voltage is present at the respective

output terminal.

Fuse

The fuse indicator lights when the fuse has blown or been cleared.

Use this table to help you interpret the 1771-OAD status indicators
and to troubleshoot module and system faults.

Indicator Status

Description of Fault or System Status

Action to Take

Module active ON (green)

Normal Indication.

None.

Module active ON (green) and

Output status ON (red)

Check voltage at output point on the

swing arm.

If voltage is present, take no action. If no voltage is

present, check the fuse. If the fuse is OK, replace the

module.

Module active ON (green) and

Output status OFF

No voltage.

None.

Output status OFF

Voltage on the terminal.

Replace the module.

Module active OFF and

Output status ON (red) or OFF

1. The processor is in program mode.

2. Module not functioning properly.

1. If module is in normal mode, take no action. If module

is in CSI mode replace module.

2. Check the chassis power supply andprocessor. If they

are OK, replace the module.

Fuse blown (red)

Outputs will not turn on.

Replace the fuse. If fuse replacement does not correct

the problem, replace the module.

Interpreting the Status

Indicators

Troubleshooting

Advertising