Connect wiring to the output module – Rockwell Automation 1771-OAD AC(12-120V)Output Installation Instructions User Manual

Page 9

Advertising
background image

AC (12-120V) Output Module

9

Publication 1771ĆIN024B-EN-P - November 2002

Make wiring connections to the 21 terminal field wiring arm (cat. no.
1771-WH) shipped with the module.

L1
L1
L1
L1

(Actual wiring runs in this direction.)

L2/optional

L1

ac High

ac Low

Output 00
Output 01
Output 02
Output 03
Output 04
Output 05
Output 06
Output 07
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
Output 17

L2

Output
Device

A

B

C

D

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

E

12223-I

Field Wiring Arm

Cat. No. 1771ĆWH

You must supply ac (L1) at terminals A through D

on the fieldwiring arm, as shown. You needfour

ac connections to accommodate the total required

surge rating on the module without overstressing

any single connection on the fieldwiring arm.

Jumper all ac (L1) connections together to prevent

module damage.

You must supply ac at terminals A through D on the wiring arm. You
need four ac connections to accommodate the total required surge
rating on the module without overstressing any single connection on
the field wiring arm. Jumper all ac connections together to prevent
module damage. Connect terminal E to ac Low.

!

ATTENTION

Observe proper polarity, as indicated in the
connection diagram with dc power connections.
Reverse polarity, or application of ac voltage,
could damage the module.

Connect Wiring to the

Output Module