AC (12-120V) Output Module

15

Publication 1771ĆIN024B-EN-P - November 2002

Enclosure Type Rating

None (open-style)

Keying

Between 10 and12

Between 20 and22

Fuse

12A, 250V rectifier fuse (1/4 x 1Ć1/4 inch), Bussman GBB12, IEC 127

Type F (black)

FieldWiring Arm

Standard

Optional

Catalog Number 1771ĆWH

Catalog Number 1771ĆWHF (fused)

Wiring Arm Screw Torque

9 pound-inches (1.02Nm)

Relay Compatibility

700-CL110A1

700-HB32A1

700-HC14A1

700-HC14A1-4

700-HF32A1

700-HT12AA1

100-A09

100-A18

100-A30

Certifications

(when product is marked)

UL

UL ListedIndustrial Control Equipment

CSA

CSA CertifiedProcess Control Equipment

CSA

CSA CertifiedProcess Control Equipment for Class I,

Division 2 Group A, B, C, D Hazardous Locations

CE

2

European Union 89/336/EEC EMC Directive,

compliant with:

EN 50082-2, Industrial Immunity

EN 61236, Meas./Control/Lab., Industrial Requirements

EN 61000-6-2, Industrial Immunity

EN 61000-6-4, Industrial Emissions

CE

2

European Union 73/23/EEC LVD Directive,

compliant with:

EN 61131-2, Programmable Controllers

C-Tick

2

Australian Radiocommunications Act, compliant with:

AS/NZS 2064, Industrial Emissions

1

You use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Industrial

Automation Wiring and Grounding Guidelines.

2

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details