Using appl_stddrv() – Rockwell Automation 6001-F2E AB STANDARD DRIVER SFTW User Manual

Page 15

Advertising
background image

Writing Your Own Application Program

Chapter 4

4-2

After you have initialized the Standard Driver with the Open_StdDrv()
function call, you are ready to communicate. You can use the
Appl_StdDrv() function call (Application Library) or the Send_StdDrv()
function call or a combination of both. Use the SendStdDrv() function
call to format commands not supported by the Application Library. See
table 4.B for a list of commands supported by the Application Library.

The Appl_StdDrv() function formats DH-485 messages for the basic
command set and transmits them over the DH-485 network. Use the
Appl_StdDrv() with the selected PLC application symbol and
Appl_StdDrv() message block data structure. The application symbols
and the message block data structure are defined in the STDDRV.H header
files. Use the following format and parameters:

Format for Appl_StdDrv()

The Appl_StdDrv() function call is shown below:

status = Appl_StdDrv(SYMBOL, SD_FB *);

Parameter

Type

Description

SYMBOL

int

identifies the support routine symbol (see table 4.B)

SD_FB

struct

initializes the DH+ function block (see table 4.C)

See appendix D for return

status

values for the Appl_StdDrv()

function.

Parameters for Appl_StdDrv()

Table 4.B below shows the available functions (in the Application
Library) you can use with Appl_StdDrv(). Table 4.C shows the
Appl_StdDrv() message block data structure:

Table 4.B
6001-F2E Support Routines

To do this

Specify this

Diagnostic loop back testing

PLC_DLB

Read diagnostic counters

PLC_DCR

Read diagnostic status

PLC_DS

Reset diagnostic counters

PLC_RC

Basic command set unprotected read

PLC_UPR

Basic command set unprotected write

PLC_UWR

Communicating on DH-485 with
the 6001-F2E Standard Driver

Using Appl_StdDrv()