Rockwell Automation 6001-F2E AB STANDARD DRIVER SFTW User Manual

Page 51

Advertising
background image

Message Packet Formats for the
Basic Command Set

Appendix C

C-2

Byte

Status Reply

Description

19

Processor Mode
Status/Control Word
– Bit 0-4 mode:

– Bit 5
– Bit 6
– Bit 7

0 – Download
1 – Program
2 – Reserved
3 – Idle due to SUS instruction
4 – Reserved
5 – Reserved
6 – Run
7 – Test Continuous Scan
8 – Test Single Scan
9 – 31 Reserved
Forces Active
Forces Installed
Communication Active

20

Processor Mode
Status/Control Word (High
Byte)
Bit 0
Bit 2
Bit 5

Protection Power Loss
Load Memory Module on Mem Error
Major Error – Process halted

21

Program ID

(low byte)

22

Program ID

(high byte)

23

Processor RAM size (in
Kbytes)

24

Bit 0
Bits 2-7:

Directory File Corrupted
00-1F (Program Owner Node Address)
3F (No Program Owner)

Advertising