Message Packet Formats for the
Basic Command Set
Appendix C
C-2
Byte
Status Reply
Description
19
Processor Mode
Status/Control Word
– Bit 0-4 mode:
– Bit 5
– Bit 6
– Bit 7
0 – Download
1 – Program
2 – Reserved
3 – Idle due to SUS instruction
4 – Reserved
5 – Reserved
6 – Run
7 – Test Continuous Scan
8 – Test Single Scan
9 – 31 Reserved
Forces Active
Forces Installed
Communication Active
20
Processor Mode
Status/Control Word (High
Byte)
Bit 0
Bit 2
Bit 5
Protection Power Loss
Load Memory Module on Mem Error
Major Error – Process halted
21
Program ID
(low byte)
22
Program ID
(high byte)
23
Processor RAM size (in
Kbytes)
24
Bit 0
Bits 2-7:
Directory File Corrupted
00-1F (Program Owner Node Address)
3F (No Program Owner)