Rockwell Automation 2711 MODBUS COMMUNICATIONS FOR PANELVIEW TERMINALS User Manual
Page 10

Publication 2711-6.9 - March 2000
10 Modbus Communications for PanelView Terminals
Port/Modem Handshake [F5]
Steps through the available options:
•
MODEM
•
RS-232
•
RS-422
•
RS-485
Note: The following delays (RTS TX, RTS Off, and CTS Timeout)
facilitate modem communications. Refer to your modem user manual
for information on the recommended delay values.
RTS TX Delay (ms) [F6]
Opens the numeric entry scratchpad. Provide a delay value of 0 to
2000 milliseconds. The RTS TX delay specifies the delay between the
assertion of the RTS signal and the transmission of the first character
of the Modbus message.
RTS Off Delay (ms) [F7]
Opens the numeric entry scratchpad. Provide a delay value of 0 to
2000 milliseconds. The RTS Off delay specifies the delay between the
transmission of the last character of the Modbus message and the
assertion of the RTS signal.
CTS Timeout (ms) [F8]
Opens the numeric entry scratchpad. Provide a timeout between 0 to
2000 milliseconds. The CTS timeout specifies the maximum allowable
delay between the assertion of the RTS signal by the PanelView
terminal and the assertion of the CTS signal by the modem.
Exit [F10] or [F16]
Returns to the Configuration Mode menu.