Modicon controller data table, Data and address types – Rockwell Automation 2711 MODBUS COMMUNICATIONS FOR PANELVIEW TERMINALS User Manual

Page 15

Advertising
background image

Publication 2711-6.9

Modbus Communications for PanelView Terminals 15

Data and Address Types

Not all of the data types are compatible with every address type. The
following table shows the Address Type available based on the
selected data type.

Modicon Controller Data
Table

Modicon controllers store read and write address spaces in the
following data table locations.

Note: The PanelView does not require data addresses that conform to
the address ranges provided in the following table. For each address
type, the PanelView terminal supports address ranges from 0 to 65535.
For example, for a discrete input status at address 40000, the full
address representation would be 140000.

Data Type

Compatible Address Type(s)

Bit

Input Status, Output Coil

4BCD

All Address types

Unsigned Integer

Input Register, Holding Register

Signed Integer

Input Register, Holding Register

IEEE Float

Input Register, Holding Register

Bit Array

Input Status, Output Coil

Character Array

Input Register, Holding Register

Address

Address Type

Data Access

Description

0xxxxx

Discrete Output
or Coil (Internal)

Bit Read or Write

Use to drive a real output through an output module or to
set one or more internal coils.
A coil can be used to drive multiple contacts.

1xxxxx

Discrete
Input Status

Bit Read Only

Use to drive contacts in the logic program. The Input state
is controlled by an input module.

3xxxxx

Input Register

Word Read Only

Holds numeric inputs from an external source (for
example, a thumb wheel entry, an analog signal or data
from a high speed counter). A 3x register can also store
16 contiguous discrete signals that are entered into the
register in either binary or binary coded decimal (BCD)
formats.

4xxxxx

Output
Holding Register

Word Read and
Write

Use to store numerical (decimal or binary) information or
to send the information to an output module.

6xxxxx

Extended
Memory Register

Access through
Logic Program only

Use to store information in an extended memory area.
Only available in PLCs with 24 bit CPUs that support
extended memory such as the 984B, E984–785 and
Quantum series of PLCs.