Publication 2711-6.9

Modbus Communications for PanelView Terminals 13

3. Under Terminal, edit the following parameters:

4. Click OK to exit and return to the Terminal Setup dialog.

Specify:

To:

Slave Response
Timeout (msec)

Enter a value between 20 and 5000 milliseconds. The
default is 250. This timeout specifies the time, after a
command is sent by the PanelView terminal, that an error
is indicated by no response from the slave device.

Baud Rate

Select the baud rate of the Modbus link. The available
baud rates are:
300
1200
4800
9600 (Default Setting)
19200
28800
38400

Data Bits/Parity

Select Number of Data Bits and Parity:
8/ODD
8/EVEN
8/NONE (Default Setting)

Note: Serial communications occur with 1 stop bit.

Port Configuration/
Modem Handshaking

Select the communication port option:
RS232 (Default)
Modem
RS422
RS485

The Following Only Appear when Modem is Selected

RTS TX Delay (msec)

Enter a value between 0 and 2000 milliseconds. The
default is 0. This delay occurs between the asserting of
RTS and the transmission of the first character of data.

RTS Off Delay (msec)

Enter a value between 0 and 2000 milliseconds. The
default is 0. This delay occurs between the last data
character transmitted and the deasserting of RTS.

CTS Timeout (msec)

Enter a value between 0 and 2000 milliseconds. The
default is 100. This timeout specifies the delay between
the assertion of the RTS signal by the PanelView terminal
and assertion of the CTS signal by the modem.