6 Modbus Communications for PanelView Terminals

Making Modbus
Connections

The PanelView Modbus protocol communicates with other devices
over an RS-232 (point-to-point) or RS-485/RS-422 (multi-drop) serial
link. Refer to the following pinout information to connect the
PanelView to a Modbus network.

Important: Follow the Modbus network layout and design as
specified by the user manual for your programmable controller.

Line Termination

The device at each end of an RS-485/422 network should be
terminated. A termination switch is provided on the PanelView (see
figure above). Enabling line termination provides an RC line
termination of .01mF and 120

.

Do not use line termination for RS-232

communications. Do not terminate devices between the network
ends.

ATTENTION

!

Use a nonconducting probe to change the line
termination switch. Do not use a graphite pencil or
other conductive material. Failure to use a
nonconducting tool, may result in damage to the
PanelView.

PanelView

Refer to next page for a
description of pinout connections.

OFF = termination is off
ON = line terminated

Line Termination

DIP Switch for RS-485/422

OFF

ON

PanelView Modbus Connector

1

2

Not Used

1

5

9

6