22 PanelView Component HMI Terminals

Publication 2711C-IN001H-EN-P - July 2014

PanelView Component devices have been tested to operate with 2711P-RSACDIN and 1606-XLP power
supplies. To use another power supply, review the criteria in the table.

Remove the Power Terminal Block

PanelView Component terminals ship with a power terminal block installed. You can remove the power
terminal block for ease of installation, wiring, and maintenance.

Follow these steps to remove the terminal block.

1. Insert the tip of a small, flat-blade, screwdriver into the terminal block access slot.

Power Supply Criteria

If the PanelView Component HMI

Use a

Description

Connects to equipment with isolated
communication ports

SELV or PELV power supply

Other equipment can share this power
supply with the PanelView Component
device provided that no ground loops
are created. A PELV power source
internally connects the negative power
terminal to chassis ground.

Does not connect to other equipment

Connects to equipment with nonisolated
communication ports

Dedicated, isolated, and
ungrounded SELV source to
power each terminal

This prevents ground loops from
damaging the devices.

ATTENTION: Disconnect all power before installing or replacing components. Failure to
disconnect power may result in electrical shock or damage to the terminal.

WARNING: When you connect or disconnect the Removable Power Terminal Block (RTB) while
the module is powered, an electrical arc can occur. This could cause an explosion in hazardous
location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.