Interpret the LED Indicators at Startup

The C400, C600 and C1000 terminals have indicators on the back of the unit to isolate operating problems.

Comm indicator for communications

Fault indicator for hardware faults

At startup, the Fault indicator is off, except for a few brief flashes, and the Comm indicator is on. If the
indicators remain off, check the power cable. After a successful startup, both indicators are off and controlled
by the application running on the terminal.

The table shows the indicator states if the terminal stops during startup.

Battery Replacement

The C400, C600 and C1000 terminals contain a lithium battery that is intended to be replaced during the
life of the product. The battery provides battery backup for the real-time clock.
It is not used for application backup or retention.

Fault Indicator States During Startup

Fault (Red)
Indicator State

Comm (Green)
Indicator State

Description

Recommended Action

Potentially recoverable errors

Blinking

Off

Last firmware download failed.

Reload the firmware.

Blinking

Blinking

EBC boot loader firmware failed or
is missing.

Reload the firmware.

Blinking

On

Windows CE OS firmware failed or
is missing.

Reload the firmware.

Nonrecoverable or fatal errors

On

Off

Fatal hardware error.

Replace the terminal.

On

Blinking

Fatal display hardware error.

Replace the terminal.

WARNING: Verify that power has been removed from the terminal prior to replacing the battery.
Work in a static free environment and wear a properly grounded electrostatic discharge (ESD)
wristband. Be careful when touching any of the exposed electronic components to prevent
damage from ESD.