Install the terminal, Minimum spacing, Mounting angle – Rockwell Automation 2711C-xxxx PanelView Component HMI Terminals Installation Instructions User Manual

Page 9: Panel guidelines

Advertising
background image

PanelView Component HMI Terminals 9

Publication 2711C-IN001H-EN-P - July 2014

Install the Terminal

Before installing the terminal in a panel, review minimum clearances, panel guidelines, panel cutout
dimensions, and product dimensions.

Minimum Spacing

Plan for adequate space around the terminal, inside the enclosure, for ventilation and cabling. Consider heat
produced by other devices in the enclosure. The ambient temperature around the terminal must be 0…50 °C

(32… 122 °F).

Mounting Angle

You can mount the terminal vertically against the panel, or tilted forward or backwards, up to a 45° angle. For
mounting angles greater than 45°, the operating temperature is restricted to 40 °C (104 °F).

Panel Guidelines

Supporting panels must be at least 16 gauge to provide proper sealing against water and dust and to provide
proper support. The panel surface must be flat and free of imperfections to maintain an adequate seal and
NEMA Type ratings.

PanelView Component

Top

Bottom

Sides

Back

C200 Function Key
C300 Touch

51 mm (2 in.)

102 mm (4 in.)

25 mm (1 in.)

13 mm (0.5 in.)

C200 and C300 Keypad
C600 Touch
C400 Touchscreen and function
keys

51 mm (2 in.)

C1000 Touch

25 mm (1 in.)

WARNING: When you insert or remove the SD Card while power is on, an electrical arc
can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

TIP

The minimum spacing requirements are sufficient for connecting cables and inserting or
removing a memory card. Plan for additional clearance if using the USB host port on the
back of the unit.