Certifications, Environmental specifications – Rockwell Automation 2711C-xxxx PanelView Component HMI Terminals Installation Instructions User Manual

Page 32

Advertising
background image

32 PanelView Component HMI Terminals

Publication 2711C-IN001H-EN-P - July 2014

Temperature, surrounding, max

50 °C (122 °F)

Heat dissipation
C200 and C300
C400
C600
C1000

16 BTU/hr
24 BTU/hr
32 BTU/hr
58 BTU/hr

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
15 g @ 11 ms

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
3V/m with 1 kHz sine-wave 80% AM from 1400…2000 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B Immunity

IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±1 kV @ 5 kHz on communication ports

Surge Transient Immunity

IEC 61000-4-5:
±500V line-line(DM) and ±1 kV line-earth(CM) on DC power ports
±1 kV line-earth(CM) on communication ports

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications

Certifications (when product is
marked)

(1)

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File

E113724.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S.

and Canada. See UL File E10314. - For 2711C-T4T only

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions

Environmental Specifications