The 7Ćsegment LED provides detailed information on the status of the
module. If the LED displays any number from 0" through 9"
inclusive or b," the module is malfunctioning and has not passed
one of its powerĆup diagnostics. Three other possible displays
indicate that the module has not been set up properly or that there is
a fault somewhere else in the system. See figure 2.2 for an
explanation of fault codes.
0
CPU failed powerĆup diagnostic
1
EPROM failed powerĆup diagnostic
2
RAM failed powerĆup diagnostic
3
CTC failed powerĆup diagnostic
4
SIO failed powerĆup diagnostic
6
DPM failed powerĆup diagnostic
7
MMU failed powerĆup diagnostic
9
PIO failed powerĆup diagnostic
bWatchdog failed powerĆup diagnostic
C
Communication line status. Displayed only if the link has
not been configured by a DCS application task.
d
System (backplane) watchdog failed. Board is operational
but will not receive data until the watchdog is reset.
E
Power failure. This code is normally displayed from the
time that a power failure is detected until power is lost.
Fault
Code
Explanation
Figure 2.2Ć LED Fault Codes