0 diagnostics and troubleshooting, 1 no activity on serial line – Rockwell Automation 57C428 Toledo Scale Interface Module User Manual

Page 27

Advertising
background image

5Ć1

5.0 DIAGNOSTICS AND

TROUBLESHOOTING

This section explains how to troubleshoot the module and field

connections. If you cannot determine the problem, the unit is not

userĆserviceable.

5.1

No Activity on Serial Line

Problem: No data is being received on the serial line. You can

confirm this by monitoring the values in register 14Ć18. If they do not

change regularly, no data is being received. The possible causes of

this error are a programming error or a malfunctioning module. It is

also possible that the transmitter is malfunctioning, or that the serial

line is not connected or is connected to the wrong transmitter. Use

the following procedure to isolate the problem:
Step 1.

Verify that the module has been configured correctly.
The LED on the module faceplate should be blank. If it is,

verify that the baud rate in register 21 is the same as the

baud rate of the transmitting device.
If the LED on the module faceplate displays the letter C,"

the module has not been configured correctly. Review

your rack configuration as well as the programming

statements to configure the module.

Step 2.

Verify that the module is connected to the correct

transmitter.
Check the cabling between the module and the

transmitter. Make certain that the proper devices are

connected together, that all the connections are secure,

and that the proper signals are connected together. Refer

to Appendix C for DĆshell connections and to figure 4 for

the proper connector on the transmitting device.

Step 3.

Verify that the serial link is working.
Connect an oscilloscope to the transmitter terminals on

the Toledo Scale digital indicator. The oscilloscope should

display a square wave with periods equal to the values in

figure 5.1 when the device is transmitting. If it does not

display a square wave, the transmitter is malfunctioning.

Volts

ąąą1200 baud = 833 microseconds

ąąą2400 baud = 417 microseconds

ąąą4800 baud = 208 microseconds

ąąą9600 baud = 104 microseconds

ąąă19200 baud = ă52 microseconds

time

Figure 5.1Ć Pulse Time for Different Baud Rates

Advertising