0 mechanical/electrical description, 1 mechanical description, 2 electrical description – Rockwell Automation 57C428 Toledo Scale Interface Module User Manual

Page 9

Advertising
background image

2Ć1

2.0 MECHANICAL/ELECTRICAL

DESCRIPTION

The following is a description of the faceplate LEDs, field termination

connectors, and electrical characteristics of the field connections.

2.1

Mechanical Description

The Toledo Scale Interface module is a printed circuit board

assembly that plugs into the backplane of the DCS5000/AutoMax

rack. It consists of a printed circuit board, a faceplate, and a

protective enclosure. The faceplate contains tabs at the top and

bottom to simplify removing the module from the rack. Module

dimensions are listed in Appendix A.
The faceplate of the module contains a 25 pin D" shell connector for

an RSĆ232C serial I/O link. For diagnostic purposes, the faceplate

contains one sevenĆsegment LED and a green status light that

indicates when the board is operational (ON) or malfunctioning

(OFF). There are also two thumbwheel switches on the faceplate of

the module. These switches are not used in this application. See

figure 2.1.
The back of the module contains two edge connectors that attach to

the system backplane.

2.2

Electrical Description

The interface module contains a 4 mhz Z80 microprocessor.

Processor memory consists of 16K bytes of EPROM memory for the

communication software, 8K bytes of RAM for local data storage, and

4K words of dual port memory. The module is equipped with a

RSĆ232C serial I/O port, a programmable baud rate generator, and

the necessary circuitry to interface with the system backplane. Refer

to the block diagram in Appendix B.
This module also contains a watchdog timer, used to detect hardware

failures. The watchdog is enabled whenever power is turned on to

the module. If a processor is unable to reset the watchdog, an

interrupt will be generated to stop the processor. The dual port

memory will be disabled so that it cannot be accessed by the user's

application software.
There is one green status light and one 7Ćsegment LED on the

faceplate of the module. The status light is labeled OK". When the

light is on, the module has passed its powerĆup diagnostics and the

watchdog timer has not timed out.

Advertising