Connecting dc power – Rockwell Automation 2711 PanelView 300 Keypad Terminal Installation Instructions User Manual

Page 10

Advertising
background image

10 PanelView 300 Keypad Terminals

Publication 2711-IN027C-EN-P - February 2009

Connecting DC Power

All of the PV300 terminals (Catalog No. 2711-K3AxxL1) connect to a 24V DC power
source.

The table below shows the electrical ratings for the DC versions of the terminals.
Electronic circuitry and an internal fuse protect the terminals from reverse polarity
and over-voltage conditions.

The PanelView 300 terminal is designed for safe use when installed in a suitably
rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.

To connect DC power to the PV300 keypad terminal:

1. Secure the DC power wires to the terminal block screws.

Terminal Type

Supply Voltage

Power Consumption

PV300 Keypad

18…32V DC,
(24V DC nominal), Class 2 Power Supply

6 Watts (0.25 Amps at 24V DC)

ATTENTION

Do not connect the PanelView terminal to an AC power source. Connecting to an AC
power source may damage the terminal.

ATTENTION

Use only a Safety Extra Low-Voltage (SELV) power supply as a source for the
PanelView 300 terminal. A SELV power supply does not exceed 42.4V DC.

IMPORTANT

The terminals are rated for 30 - 14 AWG copper wire. Tighten to 0.57 N•m (5 lb•in).

Advertising