Connecting DC Power
All of the PV300 terminals (Catalog No. 2711-K3AxxL1) connect to a 24V DC power
source.
The table below shows the electrical ratings for the DC versions of the terminals.
Electronic circuitry and an internal fuse protect the terminals from reverse polarity
and over-voltage conditions.
The PanelView 300 terminal is designed for safe use when installed in a suitably
rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.
To connect DC power to the PV300 keypad terminal:
1. Secure the DC power wires to the terminal block screws.
Terminal Type
Supply Voltage
Power Consumption
PV300 Keypad
18…32V DC,
(24V DC nominal), Class 2 Power Supply
6 Watts (0.25 Amps at 24V DC)
ATTENTION
Do not connect the PanelView terminal to an AC power source. Connecting to an AC
power source may damage the terminal.
ATTENTION
Use only a Safety Extra Low-Voltage (SELV) power supply as a source for the
PanelView 300 terminal. A SELV power supply does not exceed 42.4V DC.
IMPORTANT
The terminals are rated for 30 - 14 AWG copper wire. Tighten to 0.57 N•m (5 lb•in).