Rockwell Automation 2080-LC10-12AWA_12QWB_12QBB_12DWD Micro810 12 Point 24V/12V DC Programmable Controllers User Manual

Page 13

Advertising
background image

Micro810 12 Point Programmable Controllers 13

Publication 2080-IN006B-EN-P - April 2014

North American
temp code

T5

Insulation
stripping length

7 mm (0.28 in.)

Isolation voltage

250V
(continuous),
Reinforced
Insulation Type,
I/O to Aux and
Network, Inputs
to Outputs.
Type tested for
60 s @
3250V DC, I/O to
Aux and Network,
Inputs to Outputs

250V (continuous), Reinforced
Insulation Type, I/O to Aux and
Network, Inputs to Outputs
Type tested for 60 s @ 720V DC,
Inputs to Aux and Network, 3250V DC
Outputs to Aux and Network, Inputs to
Outputs

50V (continuous),
Reinforced
Insulation Type,
I/O to Aux and
Network, Inputs
to Outputs
Type tested for
60 s @ 720V DC,
I/O to Aux and
Network, Inputs
to Outputs

AC input filter
setting

16 ms for all embedded inputs
Through the Connected Components Workbench software, go to the
Embedded I/O configuration window to re-configure the filter setting for each
input group.

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication

1770-4.1

.

Non-isolated AC Inputs (2080-LC10-12AWA)

Attribute

Value

On-state voltage, nom

120/240 V AC

On-state voltage, min

79 V AC

On-state voltage, max

265 V AC

Off-state voltage, max

40 V AC

Operating frequency, nom

50/60 Hz

Input impedance

423.7 k

Ω

Operating frequency

47…63 Hz

General Specifications

Attribute

2080-LC10

12AWA

12QWB

12DWD

12QBB

Advertising