Rockwell Automation 2080-LC10-12AWA_12QWB_12QBB_12DWD Micro810 12 Point 24V/12V DC Programmable Controllers User Manual

Page 16

Advertising
background image

16 Micro810 12 Point Programmable Controllers

Publication 2080-IN006B-EN-P - April 2014

Temperature,
storage

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g (DIN Rail Mounted)
30 g (Panel Mounted)

Emissions

CISPR 11
Group 1, Class A

ESD immunity

IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on shielded ports

Conducted RF
immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Voltage variation

IEC 61000-4-11:
60% dip for 5 and 50 periods on AC supply ports
30% dip for 0.5 period @ 0° and 180° on AC supply ports
100% dip for 0.5 period @ 0° and 180° on AC supply ports
±10% fluctuations for 15 min on AC supply ports
>95% interruptions for 250 periods on AC supply ports

Environmental Specifications

Attribute

Value

Advertising