Mount the Module

Most applications require installation in an industrial enclosure to reduce the effects of electrical
interference and environmental exposure. Locate your controller as far as possible from power
lines, load lines, and other sources of electrical noise such as hard-contact switches, relays, and
AC motor drives. For more information on proper grounding guidelines, see the Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Mounting Dimensions and DIN Rail Mounting

Module Spacing

Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation.

DIN Rail Mounting

The module can be mounted using the following DIN rails: 35 x 7.5 x 1 mm
(EN 50 022 - 35 x 7.5) .

Before mounting the module on a DIN rail, use a flat-blade screwdriver in the DIN rail latch and
pry it downwards until it is in the unlatched position.

1. Hook the top of the DIN rail mounting area of the controller onto the DIN rail, and

then press the bottom until the controller snaps onto the DIN rail.

2. Push the DIN rail latch back into the latched position.

Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAHJ35)
for vibration or shock environments.

45054

Mounting dimensions do not
include mounting feet or DIN rail
latches.

75 mm (2.95 in.)

59 mm (2.32 in.)

91 mm (3.58 in.)